Electrical Wire Color Codes vs. Wire Ampacity Ratings

Comparing 2 standards across 23 specifications. 23 key differences identified.

Comparing:
Electrical Wire Color Codes
Wire Ampacity Ratings

AC electrical wiring color codes distinguish Line (hot), Neutral, and Ground conductors, standardized in the US under NEC (120/240V Black/Red/White and 277/480V Brown/Orange/Yellow) and internationally under IEC 60446 (Brown/Black/Grey Line, Blue Neutral, Green-Yellow Ground).

View full Electrical Wire Color Codes spec sheet →

National Electrical Code (NEC) Table 310.16 establishes allowable conductor ampacities based on conductor material (Copper vs Aluminum), ambient temperature, and insulation thermal ratings (60°C TW/NM-B Romex, 75°C THWN, 90°C THHN).

View full Wire Ampacity Ratings spec sheet →

Specification Comparison Table

23 Parameters
Parameter / Spec
Governing Standards
NEC Article 200/250 (US) / IEC 60446 / BS 7671 (Europe/UK)
US 120V / 240V Phase A (Hot)
Black
US 120V / 240V Phase B (Hot)
Red
US 120V / 208V Phase C (Hot 3-Phase)
Blue
US 120V / 240V Neutral
White (Continuous white or gray outer finish per NEC 200.6)
US 277V / 480V Commercial 3-Phase (Wye)
Phase A: Brown | Phase B: Orange | Phase C: Yellow | Neutral: Gray (conventional scheme; this is a symmetrical wye system with no high-leg condition)
US 120V / 240V High-Leg Delta (4-Wire, 3-Phase)
Phase A: Black | Phase B: Orange (NEC 110.15-mandated high-leg marking, ~208V to neutral) | Phase C: Blue | Neutral: White
US Protective Earth / Ground
Bare Copper, Green, or Green with Yellow Stripe
IEC / Europe Phase 1 (L1)
Brown
IEC / Europe Phase 2 (L2)
Black
IEC / Europe Phase 3 (L3)
Grey
IEC / Europe Neutral (N)
Blue (Light Blue)
IEC / Europe Protective Earth (PE)
Green with Yellow Stripe (Bi-color mandate)
Governing Code
NFPA 70: National Electrical Code (NEC) Table 310.16
Small Conductor Overcurrent Rule (NEC 240.4D)
14 AWG Cu: Max 15A | 12 AWG Cu: Max 20A | 10 AWG Cu: Max 30A
14 AWG Copper (NM-B / Romex)
15 Amps (60°C column applied per NEC 334.80)
12 AWG Copper (NM-B / Romex)
20 Amps (Standard residential branch circuit)
10 AWG Copper (NM-B / Romex)
30 Amps (Clothes dryers, 30A water heaters)
8 AWG Copper (75°C THWN / NM-B)
40A (NM-B 60°C) / 50A (THWN 75°C conduit)
6 AWG Copper (75°C THWN / NM-B)
55A (NM-B 60°C) / 65A (THWN 75°C conduit)
4 AWG Copper (75°C THWN)
85 Amps (Residential subpanel feeder)
2 AWG Copper (75°C THWN)
115 Amps (100A subpanel / main feeder)
4/0 Aluminum (75°C XHHW / SE)
180 Amps under standard NEC Table 310.16 ampacity; commonly used as the minimum conductor for a 200A dwelling service under NEC's separate service-conductor allowance (Table 310.12, formerly 310.15(B)(7))