Electrical Wire Color Codes

Electrical & Wiring · 13 specs

Direct Answer

AC electrical wiring color codes distinguish Line (hot), Neutral, and Ground conductors, standardized in the US under NEC (120/240V Black/Red/White and 277/480V Brown/Orange/Yellow) and internationally under IEC 60446 (Brown/Black/Grey Line, Blue Neutral, Green-Yellow Ground).

Source: NFPA 70: National Electrical Code / IEC 60446 / BS 7671 · Last reviewed Aug 28, 2026

Specs

Governing Standards NEC Article 200/250 (US) / IEC 60446 / BS 7671 (Europe/UK)
US 120V / 240V Phase A (Hot) Black
US 120V / 240V Phase B (Hot) Red
US 120V / 208V Phase C (Hot 3-Phase) Blue
US 120V / 240V Neutral White (Continuous white or gray outer finish per NEC 200.6)
US 277V / 480V Commercial 3-Phase (Wye) Phase A: Brown | Phase B: Orange | Phase C: Yellow | Neutral: Gray (conventional scheme; this is a symmetrical wye system with no high-leg condition)
US 120V / 240V High-Leg Delta (4-Wire, 3-Phase) Phase A: Black | Phase B: Orange (NEC 110.15-mandated high-leg marking, ~208V to neutral) | Phase C: Blue | Neutral: White
US Protective Earth / Ground Bare Copper, Green, or Green with Yellow Stripe
IEC / Europe Phase 1 (L1) Brown
IEC / Europe Phase 2 (L2) Black
IEC / Europe Phase 3 (L3) Grey
IEC / Europe Neutral (N) Blue (Light Blue)
IEC / Europe Protective Earth (PE) Green with Yellow Stripe (Bi-color mandate)

US NEC vs International IEC 60446 Wire Color Comparison

Function US Residential (120/240V Split-Phase) US Commercial (277/480V 3-Phase Wye) European Union / IEC 60446 UK Pre-2004 Harmonization
Phase 1 (Line 1 / Hot) Black Brown Brown Red
Phase 2 (Line 2 / Hot) Red Orange Black Yellow
Phase 3 (Line 3 / Hot) Blue Yellow Grey Blue
Neutral (Grounded) White Gray Blue (Light Blue) Black
Ground (Protective Earth) Bare / Green Green Green-Yellow Green-Yellow

Note: the orange 'high-leg' marking is a separate NEC 110.15 requirement that applies specifically to 120/240V, 4-wire, 3-phase delta services (where one phase reads ~208V to neutral) — it is not part of the 277/480V wye scheme above, which has no high-leg conductor.

The Danger of Transatlantic Color Code Mismatches

Cross-border equipment installation carries extreme hazard due to the 2004 European Harmonization (BS 7671 / IEC 60446):

  • The Black Wire Reversal: In the United States, Black is Live/Hot (120V) and Blue is 3-phase Hot. In modern European wiring, Black is Line 2, but in legacy UK wiring (pre-2004), Black was Neutral. Connecting an imported US fixture assuming black is neutral results in an energized live chassis.
  • The Blue Wire Reversal: In the US, Blue is an energized 3-phase Line conductor. In Europe, Blue is Neutral.