Side-by-Side Comparison Electrical & Wiring

Electrical Wire Color Codes vs. Electrical Conduit

Comparing 2 standards across 22 specifications. 22 key differences identified.

Comparing:
Electrical Wire Color Codes
Electrical Conduit

AC electrical wiring color codes distinguish Line (hot), Neutral, and Ground conductors, standardized in the US under NEC (120/240V Black/Red/White and 277/480V Brown/Orange/Yellow) and internationally under IEC 60446 (Brown/Black/Grey Line, Blue Neutral, Green-Yellow Ground).

View full Electrical Wire Color Codes spec sheet →

Electrical conduit sizing is governed by the National Electrical Code Chapter 9 Table 1 40% fill rule for three or more conductors, matching raceway types including Electrical Metallic Tubing (EMT), Schedule 40/80 PVC, and Rigid Metal Conduit (RMC).

View full Electrical Conduit spec sheet →

Specification Comparison Table

22 Parameters
Parameter / Spec
Governing Standards
NEC Article 200/250 (US) / IEC 60446 / BS 7671 (Europe/UK)
US 120V / 240V Phase A (Hot)
Black
US 120V / 240V Phase B (Hot)
Red
US 120V / 208V Phase C (Hot 3-Phase)
Blue
US 120V / 240V Neutral
White (Continuous white or gray outer finish per NEC 200.6)
US 277V / 480V Commercial 3-Phase (Wye)
Phase A: Brown | Phase B: Orange | Phase C: Yellow | Neutral: Gray (conventional scheme; this is a symmetrical wye system with no high-leg condition)
US 120V / 240V High-Leg Delta (4-Wire, 3-Phase)
Phase A: Black | Phase B: Orange (NEC 110.15-mandated high-leg marking, ~208V to neutral) | Phase C: Blue | Neutral: White
US Protective Earth / Ground
Bare Copper, Green, or Green with Yellow Stripe
IEC / Europe Phase 1 (L1)
Brown
IEC / Europe Phase 2 (L2)
Black
IEC / Europe Phase 3 (L3)
Grey
IEC / Europe Neutral (N)
Blue (Light Blue)
IEC / Europe Protective Earth (PE)
Green with Yellow Stripe (Bi-color mandate)
Governing Standard
NFPA 70 (NEC) Chapter 9, Tables 1, 4, and 5
1 Conductor Maximum Fill
53% of total internal cross-sectional area
2 Conductors Maximum Fill
31% of total internal cross-sectional area
3 or More Conductors Max Fill
40% of total internal cross-sectional area (Universal Standard)
1/2" EMT Conduit
ID: 0.622 in (15.8 mm) | Total Area: 0.304 sq in | 40% Usable: 0.122 sq in (9 × 12 AWG THHN max)
3/4" EMT Conduit
ID: 0.824 in (20.9 mm) | Total Area: 0.533 sq in | 40% Usable: 0.213 sq in (16 × 12 AWG THHN max)
1" EMT Conduit
ID: 1.049 in (26.6 mm) | Total Area: 0.864 sq in | 40% Usable: 0.346 sq in (26 × 12 AWG THHN max)
2" EMT Conduit (Service Entrance)
ID: 2.067 in (52.5 mm) | Total Area: 3.356 sq in | 40% Usable: 1.342 sq in (3 × 4/0 Cu THHN)
Schedule 80 PVC vs EMT
Schedule 80 has heavy thick walls; has ~15–20% smaller internal area than EMT