Electrical Conduit vs. Wire Ampacity Ratings

Comparing 2 standards across 19 specifications. 19 key differences identified.

Comparing:
Electrical Conduit
Wire Ampacity Ratings

Electrical conduit sizing is governed by the National Electrical Code Chapter 9 Table 1 40% fill rule for three or more conductors, matching raceway types including Electrical Metallic Tubing (EMT), Schedule 40/80 PVC, and Rigid Metal Conduit (RMC).

View full Electrical Conduit spec sheet →

National Electrical Code (NEC) Table 310.16 establishes allowable conductor ampacities based on conductor material (Copper vs Aluminum), ambient temperature, and insulation thermal ratings (60°C TW/NM-B Romex, 75°C THWN, 90°C THHN).

View full Wire Ampacity Ratings spec sheet →

Specification Comparison Table

19 Parameters
Parameter / Spec
Governing Standard
NFPA 70 (NEC) Chapter 9, Tables 1, 4, and 5
1 Conductor Maximum Fill
53% of total internal cross-sectional area
2 Conductors Maximum Fill
31% of total internal cross-sectional area
3 or More Conductors Max Fill
40% of total internal cross-sectional area (Universal Standard)
1/2" EMT Conduit
ID: 0.622 in (15.8 mm) | Total Area: 0.304 sq in | 40% Usable: 0.122 sq in (9 × 12 AWG THHN max)
3/4" EMT Conduit
ID: 0.824 in (20.9 mm) | Total Area: 0.533 sq in | 40% Usable: 0.213 sq in (16 × 12 AWG THHN max)
1" EMT Conduit
ID: 1.049 in (26.6 mm) | Total Area: 0.864 sq in | 40% Usable: 0.346 sq in (26 × 12 AWG THHN max)
2" EMT Conduit (Service Entrance)
ID: 2.067 in (52.5 mm) | Total Area: 3.356 sq in | 40% Usable: 1.342 sq in (3 × 4/0 Cu THHN)
Schedule 80 PVC vs EMT
Schedule 80 has heavy thick walls; has ~15–20% smaller internal area than EMT
Governing Code
NFPA 70: National Electrical Code (NEC) Table 310.16
Small Conductor Overcurrent Rule (NEC 240.4D)
14 AWG Cu: Max 15A | 12 AWG Cu: Max 20A | 10 AWG Cu: Max 30A
14 AWG Copper (NM-B / Romex)
15 Amps (60°C column applied per NEC 334.80)
12 AWG Copper (NM-B / Romex)
20 Amps (Standard residential branch circuit)
10 AWG Copper (NM-B / Romex)
30 Amps (Clothes dryers, 30A water heaters)
8 AWG Copper (75°C THWN / NM-B)
40A (NM-B 60°C) / 50A (THWN 75°C conduit)
6 AWG Copper (75°C THWN / NM-B)
55A (NM-B 60°C) / 65A (THWN 75°C conduit)
4 AWG Copper (75°C THWN)
85 Amps (Residential subpanel feeder)
2 AWG Copper (75°C THWN)
115 Amps (100A subpanel / main feeder)
4/0 Aluminum (75°C XHHW / SE)
180 Amps under standard NEC Table 310.16 ampacity; commonly used as the minimum conductor for a 200A dwelling service under NEC's separate service-conductor allowance (Table 310.12, formerly 310.15(B)(7))