Side-by-Side Comparison Electrical & Wiring

AWG Wire Sizes vs. Electrical Conduit Fill Capacity

Comparing 2 standards across 17 specifications. 17 key differences identified.

Comparing:
AWG Wire Sizes
Electrical Conduit Fill Capacity

The American Wire Gauge (AWG / ASTM B258) system standardizes solid round electrical conductor diameters based on a logarithmic ratio where 36 AWG equals 0.0050 inches (0.127 mm) and 4/0 (0000) AWG equals 0.4600 inches (11.684 mm) across 39 stepping steps.

View full AWG Wire Sizes spec sheet →

Electrical conduit fill capacity is strictly regulated under the National Electrical Code (NEC Chapter 9, Tables 1, 4, and 5) limiting total conductor cross-sectional area to 40% of internal conduit area for three or more wires, preventing heat buildup and insulation damage during wire pulls.

View full Electrical Conduit Fill Capacity spec sheet →

Specification Comparison Table

17 Parameters
Parameter / Spec
Governing Standards
ASTM B258 / National Electrical Code (NEC) Chapter 9 Table 8 NFPA 70 (NEC) Chapter 9 / Annex C (Conduit Fill Tables) / NEMA Standards
Geometric Stepping Ratio
Ratio between consecutive gauges is 39√(0.4600 / 0.0050) ≈ 1.1229322
Area Doubling Rule of Thumb
Decreasing by 3 gauge numbers doubles conductor cross-sectional area and halves resistance
Diameter Doubling Rule
Decreasing by 6 gauge numbers doubles conductor diameter
14 AWG (15A Residential Lighting)
Dia: 1.628 mm (0.0641 in) | Area: 2.08 mm² (4,110 cmil) | 8.286 Ω/km
12 AWG (20A Small Appliance)
Dia: 2.053 mm (0.0808 in) | Area: 3.31 mm² (6,530 cmil) | 5.211 Ω/km
10 AWG (30A Water Heater / Dryer)
Dia: 2.588 mm (0.1019 in) | Area: 5.26 mm² (10,380 cmil) | 3.277 Ω/km
8 AWG (40-50A Electric Range)
Dia: 3.264 mm (0.1285 in) | Area: 8.37 mm² (16,510 cmil) | 2.061 Ω/km
6 AWG (55-65A Subpanel / Cooktop)
Dia: 4.115 mm (0.1620 in) | Area: 13.30 mm² (26,240 cmil) | 1.296 Ω/km
4/0 AWG (200A Residential Service)
Dia: 11.684 mm (0.4600 in) | Area: 107.2 mm² (211,600 cmil) | 0.1608 Ω/km
The NEC 40% Fill Rule
1 Conductor: 53% max | 2 Conductors: 31% max | 3 or More Conductors: 40% max cross-sectional fill
1/2" EMT Conduit (Trade Size 16)
Internal Area: 0.304 sq in | 40% Fill: 0.122 sq in | Max 9× 14 AWG, 6× 12 AWG, or 4× 10 AWG THHN wires
3/4" EMT Conduit (Trade Size 21)
Internal Area: 0.533 sq in | 40% Fill: 0.213 sq in | Max 16× 14 AWG, 10× 12 AWG, or 7× 10 AWG THHN wires
1" EMT Conduit (Trade Size 27)
Internal Area: 0.864 sq in | 40% Fill: 0.346 sq in | Max 26× 14 AWG, 16× 12 AWG, or 12× 10 AWG THHN wires
1-1/4" EMT Conduit
Internal Area: 1.496 sq in | 40% Fill: 0.598 sq in | Ideal for 100A subpanel feeds (3× 1 AWG + 6 AWG ground)
2" EMT Conduit
Internal Area: 3.356 sq in | 40% Fill: 1.342 sq in | Standard 200A residential service mast (3× 2/0 Cu or 4/0 Al)
Conduit Types
EMT (Electrical Metallic Tubing), Schedule 40 PVC, Schedule 80 PVC (Thick wall), Rigid Metal (RMC)